The number printed on a battery — 100 Ah, 200 Ah — is not what you actually get to use. Three things eat into it: the depth of discharge the chemistry will tolerate, the inverter efficiency if there is one, and, on lead-acid banks, Peukert's law — draw harder and the battery gives back less.

This calculator walks the whole chain, from the rated capacity down to runtime in hours, and shows what each step takes away.

Depth of discharge is not a loss: the energy is there, but using it shortens the battery's life. Running a lead-acid battery down to 20 % state of charge cuts its cycle count by three or four — which is why 50 % is the figure everyone works to.

The battery and its load

The battery

The figure printed on the case. Batteries in parallel add their amp-hours.

12, 24 or 48 V. Batteries in series add their volts, not their amp-hours.

A starting point for the next two fields, which you are free to change to match your battery's datasheet.

Typical for this chemistry: 50 %.

The load

Everything running at the same time, added up, in watts.

85 to 93 % for a 12 V to 230 V inverter. Use 100 for a DC load wired straight to the battery.

Peukert's law (lead-acid batteries)

Tick it for flooded, AGM and gel. Barely measurable on lithium.

1 means no effect. Typical here: 1.15. Referenced to the C20 rate.

rated capacity1,200 Wh−600 Whusable energy (depth of discharge)600 Whenergy delivered to the load540 Whruntime = energy delivered / load =4 h 30 min
Worked example, drawn to the demonstration values: each step takes its share, and the dashed boxes show what has gone. The figure redraws with your own values once you calculate.

Ah, Wh and kWh: three ways to measure one reserve, and which one to compare

Capacity comes written three ways, and they are not interchangeable. Amp-hours are charge: how many amps for how many hours, at the battery's own voltage. Watt-hours (and kWh) are energy: Ah × V. A 100 Ah bank at 12 V is 1,200 Wh. The same 100 Ah at 24 V is 2,400 Wh — twice the work, same Ah on the sticker.

Compare Wh (or kWh). Always. Two “100 Ah leisure batteries” on a shelf are not a match if one is 12 V and the other is 24 V. Ah is useful once the voltage is fixed and you are thinking in current; it is a trap when you are shopping. This calculator converts to Wh first, then applies DoD and inverter efficiency, which is why the runtime is not “Ah ÷ amps” on a good day.

Depth of discharge against cycle life: the real price of the energy you take

DoD is the slice you take: 80 Ah out of 200 Ah is 40 %. Cycle life is how many times you can do that before the bank is junk. Lead-acid is unforgiving: sit at 80 % DoD every day and you get a fraction of the cycles you would get at 30–50 %. The energy you “saved” by buying a smaller bank is paid back as a replacement two years early.

DoD = Ah taken / Ah rated · usable Ah = Ah rated × DoDmax

Oversizing so that a normal day only dips 30–40 % is, for flooded and AGM, often cheaper than buying the smallest bank that can limp through one night. Lithium is happier deep: 80–90 % DoD is the point of paying for it. The DoD field on this page is not a suggestion from a brochure. It is the remaining life of the bank, typed in as a percentage.

Flooded, AGM, gel, LiFePO4: what each chemistry genuinely accepts

  • Flooded (wet) lead-acid — about 50 % DoD if you want it to last. Needs water, ventilation for hydrogen, an upright box. Cheap per rated Ah, not cheap per usable Ah.
  • AGM — around 50–60 % DoD, sealed, handles vibration and a punch of current. A decent leisure battery if you will not abuse it.
  • Gel — can be taken a bit deeper (around 70 % in a slow discharge) and hates a fat charge current. Fine for a small, quiet bank. Easy to ruin with a charger meant for flooded.
  • LiFePO4 (lithium iron phosphate) — 80–90 % DoD, high round-trip efficiency, high current, a BMS in the box. A 100 Ah lithium pack is closer to 90 usable Ah; a 100 Ah flooded sitting at 50 % DoD is 50.

That is why a “smaller” lithium bank often outruns a “bigger” lead-acid one on this page. The chemistry field is doing as much work as the Ah field.

Peukert's law without the maths, and why lithium escapes it

Lead-acid gives you less Ah if you pull harder. The plates cannot feed the reaction fast enough, voltage sags, and a chunk of the nameplate capacity is simply not there at that current. Peukert's exponent k (typically 1.1–1.3 for lead-acid) captures that. k = 1 means no penalty. This page applies it when the chemistry warrants it, using the 20-hour rating as the reference.

Ceffective = C × (C / (I × 20))k − 1

Lithium iron phosphate barely notices. Within the BMS current limit, 1C and 0.05C deliver almost the same Ah. That is one of the reasons a lithium bank loves an inverter surge (a kettle, a microwave) that would make a lead-acid bank fall over. Anyway, if you tick a lead-acid chemistry and a fat load, believe the shorter runtime. The nameplate was a C20 number, not a promise at 0.5C.

C20, C10 and C5 ratings: reading a datasheet without mixing up the rate

Capacity is always “at this discharge time”. C20 means 20 hours: a 100 Ah C20 cell is a 5 A load for 20 h. C10 is a faster test, a smaller Ah number on the same battery. C5 smaller still. Solar cycling is slow — C20 or even C100 is the honest figure. A starter burst is the other end of the scale: CCA, not C20, is the number that matters, and a leisure battery is the wrong tool.

Datasheets that quote a fat Ah at C100 and a shy one at C5 are not lying twice. They are showing Peukert in a table. Type the C20 figure into this calculator unless you know you have a C10 plate, and let the Peukert correction handle a faster load.

Series or parallel: adding volts or adding amp-hours

Series stacks voltage; Ah stay the same. Two 12 V 100 Ah in series: 24 V, 100 Ah, 2.4 kWh. Parallel stacks Ah; voltage stays put. The same two in parallel: 12 V, 200 Ah, still 2.4 kWh. Energy is the same; current on the cables is not. 12 V at the same watts is twice the amps of 24 V, which is why fat inverters and long cable runs belong on 24 or 48 V.

Never mix ages, capacities or chemistries in one bank. The weak unit is a heater and a drag on the others, in series or in parallel. Same batch, same history, a fuse per parallel string if you can.

Inverter efficiency, no-load draw and standby: the losses everyone forgets

A decent inverter is 90–95 % at a sensible load, and sulks at a few tens of watts. The efficiency field on this page covers the conversion. It does not cover the idle draw: 5–30 W with nothing plugged in, all night. On a 12 V bank, 20 W idle is 40 Ah/day. That is a day of lights, gone, before anyone boiled a kettle.

Idle Ah/day = Pidle × 24 / U

Standby (“search”, ECO) modes cut that idle dramatically and wake on a load. For a weekend boat, switching the inverter off is still the best efficiency number in the catalogue. Well, ghost loads on the DC side (alarms, routers, a USB socket that never sleeps) do the same job without an inverter at all.

Charging time: charger current, and the bulk / absorption / float stages

  1. Bulk — charger at max current, voltage climbing, up to roughly 80 % on lead-acid. Time ≈ Ah to put back / charger amps.
  2. Absorption — voltage held, current tapering, the last 20 %. Slow, and not optional on lead-acid if you want the plates to last.
  3. Float — a lower voltage to hold a full bank. Lithium often skips a long float; a LiFePO4 BMS is happier at rest than sitting on a float voltage all winter.

Count 1.5–2 × the bulk time for a full lead-acid charge, 1.1–1.2 × for lithium. A 20 A charger on a 200 Ah flooded bank is a ten-hour bulk on paper and an afternoon in the real world. Charge current limits differ: gel is fussy, flooded is thirsty, lithium will take whatever the BMS allows — often 0.5C.

What temperature does to capacity and to service life

Cold steals Ah. Lead-acid at −10 °C can be 20–30 % down; lithium more like 10–15 % on discharge. Heat does the opposite to the meter and the opposite to the calendar: every +10 °C above about 20 °C roughly halves flooded life (Arrhenius, not folklore). A battery in an engine bay is living fast.

Charging lithium below 0 °C is the one that damages cells — lithium plating on the anode — unless the BMS blocks it or a heater is in the pack. Discharge in the cold is uncomfortable. Charge in the cold without a lock-out is how you kill a new bank in a season.

Sizing a bank for a daily consumption plus three days of autonomy

Off-grid sizing is daily watt-hours, times the days you want to survive without sun or a generator, divided by the DoD you will respect, then a bit of margin. Inverter losses belong in the daily Wh, not as an afterthought.

Bank Wh = (daily Wh × days) / (DoDmax × η) · Ah = Wh / U

1,000 Wh/day, three days, 50 % DoD, no extra η: 6,000 Wh, which is 500 Ah at 12 V. Same days on LiFePO4 at 90 % DoD: about 280 Ah at 12 V. This calculator answers “how long tonight”; the formula above answers “how big a bank before we leave the yard”.

Resting voltage and state of charge: the table that replaces a monitor

A 12 V lead-acid bank, rested an hour or two with nothing going in or out:

  • 12.70 V or so — full
  • 12.40 V — about 75 %
  • 12.20 V — about 50 %
  • 12.00 V — about 25 %
  • 11.80 V and below — stop

Under load the voltage sags; on charge it soars. Neither reading is SoC. Lithium is worse as a voltmeter trick: the curve is so flat between 20 and 80 % that you need a coulomb-counting shunt. A cheap panel meter on the terminals is a mood, not a fuel gauge.

Leisure battery or starter battery: two jobs, two constructions

A starter (SLI) battery is thin plates, huge surface, a few seconds of hundreds of amps. It hates deep cycles: a few dozen at 50 % DoD and it is sulphated junk. A leisure (deep-cycle) battery is thick plates, fewer amps, hundreds to more than a thousand cycles depending on chemistry. House loads — fridge, lights, inverter — are a leisure job. The engine is a starter job. Two batteries, two cables, a split charge, and neither is doing the other's work.

A “dual-purpose” unit is a compromise that is acceptable on a small boat with one box and no room. It is still not a house bank.

C-rate, in one sentence

C-rate is current as a fraction of the rated Ah: 100 A from 100 Ah is 1C; 5 A is 0.05C. Runtime in hours is roughly 1 / (C-rate) before Peukert and DoD. This page prints it so you can see whether you are in “gentle overnight” territory or “the inverter is a starter motor” territory.

Why 24 V and 48 V keep showing up

Power is U × I. Twice the voltage, half the current, quarter the I²R in the cables if you also sized them for the old amps — or much thinner cables for the same loss. Past a couple of kilowatts of inverter, 12 V becomes a welding exercise. The Wh in the bank do not care. The cable run does.

State of health is not state of charge

SoC is how full the tank is today. SoH is how big the tank still is. A five-year flooded bank at “12.3 V rested” can look half full and actually be a 60 % tank filled to 80 %. This calculator uses the Ah you type as if they were new. If the bank has been abused, type the capacity you last measured, not the sticker from 2019.

Peukert, DoD and inverter efficiency still assume a healthy bank at the temperature you had in mind. A sulphated lead-acid, a LiFePO4 pack with a cell out of balance, or a charge below freezing will not match the runtime on the screen. Treat a shortfall against the calculation as a diagnosis, not as a reason to type a kinder DoD.