Three-phase power calculator: kW, kVA and amps

On a balanced three-phase load, apparent power is S = √3 · U · I, where U is the voltage between two phases and I is the current in one line conductor. Everything else follows from it: the current to expect, the breaker rating and the cable size.

This calculator returns all three powers at once — real in kW, reactive in kvar, apparent in kVA — plus the line current, the current in each winding for wye and delta, and, if you want it, the capacitor bank needed to raise the power factor.

The √3 belongs with the line-to-line voltage and the line current. Using the phase voltage V = U / √3, the same power reads P = 3 · V · I · cos φ. Both forms are correct; mixing them is a factor-of-√3 error, or 73 %.

The three-phase load

Supply and load

400 V on a 230/400 V supply, 480 V on 277/480 V. Between phases, not phase to neutral.

Read it off the motor nameplate or measure it. 1 for resistive heating, 0.7 to 0.9 for a loaded motor.

The first sizes an installation; the second turns a clamp-meter reading into power.

The useful power drawn — what the kWh meter bills.

Power factor correction (optional)

0.95 is the usual target for staying clear of reactive-power charges. Leave empty to skip.

φ = 31.8°P = 15.00 kWQ = 9.30 kvarS = 17.65 kVAS = √3 · U · IU = line-to-line voltage, I = line current
Worked example, drawn to the demonstration values. The angle φ is plotted at the real power factor: the lower it falls, the more the triangle stands up, and the further S — hence the current and the cable size — drifts away from the power doing work. The figure redraws with your own values.

Where the √3 comes from: adding three voltages 120° apart

Three phases, 120° apart. Line-to-line voltage is not 230 + 230. The two phase-to-neutral phasors are the same length and 120° from each other; their difference is a third phasor √3 times as long. 1.732, not 2. That is why a European low-voltage supply is 230/400 V and not 230/460.

U = √3 · V · V = U / √3

U is line-to-line (the 400 V), V is phase-to-neutral (the 230 V). The three-phase power formulas on this page use U and the line current. Write them with V instead and the √3 disappears: P = 3 · V · I · cos φ. Same watts, two spellings. Mix U with the version that already had a 3, and you are 73 % high.

Phase voltage and line voltage, and why supplies are named 230/400 V

230/400 means both numbers are on the same board. Sockets and single-phase loads live between a phase and the neutral at 230 V. Motors and three-phase heaters live between phases at 400 V. North America writes 120/208 or 277/480 the same way: the pair is V and U, always a √3 apart on a wye.

Older European plant still says 240/415. The arithmetic did not change; the nominal did, slightly. Type the voltage you actually measure, or the voltage on the nameplate of the switchgear, not a round number from a textbook printed in 1985.

Line current and winding current: what the connection really changes

Line current I is what the cable and the breaker see. Winding current is what each coil of the motor or the transformer carries.

  • Wye (star) — each winding sits on V = U/√3. Line current equals winding current.
  • Delta — each winding sits on U. Line current is √3 times the winding current: two windings feed each line.

Same shaft power, different split. Delta puts more amps on the supply cable and fewer on each winding; star does the opposite. The star-delta resistor transform is a different trick again — equivalent networks, not a motor connection.

Wye or delta: reading the motor nameplate to decide

The plate prints two voltages, say 230/400 V or 400/690 V. Lower number is delta, higher is star. A 230/400 motor on a 400 V line is a star motor in service; each winding sees 230 V. A 400/690 motor on 400 V is a delta motor. Get it backwards and you either under-flux the machine (star on a supply that wanted delta) or over-flux it until the iron saturates (delta on a supply that wanted star).

Star-delta starting needs the delta voltage to match the supply — so a 400 V network wants a 400/690 motor, not a 230/400. The starting calculator exists because this one-line reminder is the mistake that gets ordered most often.

Star-delta starting, or how to cut inrush current to a third

DOL inrush is 6–10 × In. Start in star and each winding sees U/√3; line current and torque both drop to a third of the delta DOL values. After the shaft is up (roughly 75–90 % speed), the starter flips to delta and you have full voltage, full torque, full current.

Istar = IDOL / 3 · Tstar = TDOL / 3

Cheap, six-lead, no speed control. Useless if the load needs more than a third of DOL torque to break away. A VFD or a soft starter is the other conversation.

kW, kVA and kvar: three powers, three uses, three lines on the bill

Active power P in kW is the shaft, the heat, the light — the bit the kWh meter integrates. Apparent power S in kVA is U × I × √3, what the transformer and the cables must be able to carry. Reactive power Q in kvar is the magnetising slosh, mostly from motors and transformers. The triangle is not a metaphor:

S² = P² + Q² · P = S · cos φ · Q = S · sin φ

You pay for kWh. You may also pay for a poor power factor, because the utility had to size the network for S, not for P. A motor at 0.7 lagging draws 43 % more current than the same kW at 1.0. That extra current is Q, and it is why this page offers a capacitor-bank result.

Measuring power factor without a wattmeter: the two-wattmeter method

Two wattmeters, two phases, no neutral needed. Their readings add up to the total three-phase P, even if the load is a bit unbalanced (linear load). S still wants a voltmeter and an ammeter; cos φ = P/S. A modern clamp with a power-factor mode does the same job in one jaw, on one conductor, if you trust its firmware.

The two-wattmeter trick also tells you the sign: if one instrument reads backwards, φ is past 60° and the power factor is worse than 0.5. Worth knowing before you size a bank.

Fixed, stepped or automatic correction: sizing a capacitor bank

Capacitors supply leading kvar that cancel the lagging kvar of the motors. Target is usually 0.93 to 0.95 lagging — not 1.00, which over-corrects at light load and can raise the voltage.

Qc = P · (tan φ1 − tan φ2)

  • Fixed — one block, one motor, on with the contactor. Cheap. Wrong on a load that comes and goes.
  • Stepped — a few blocks, contactors, a coarse staircase.
  • Automatic — a controller watching cos φ, stages in and out. The default on a busy board.

Detune the bank (a small series reactor) if the site has VFDs or a lot of switched-mode kit. A naked capacitor and a 5th-harmonic current are how you buy a resonance.

Power factor versus displacement factor: what harmonics do to both

Displacement factor is cos φ of the 50 or 60 Hz fundamentals — what a classical wattmeter-and-ammeter setup thought power factor was. Total power factor is P/S with every harmonic in S. On a sine-wave motor they are the same. On a six-pulse drive they are not: PF ≤ cos φ, always.

PF = P / S · cos φ = P / S1

A capacitor bank corrects displacement. It does not correct distortion. It can make distortion worse. If the clamp says 0.96 displacement and 0.78 total, the missing slice is harmonics, and more kvar will not find it.

Unbalanced loads: why the formulas above no longer apply

P = √3 · U · I · cos φ wants three equal currents 120° apart. A lighting phase piled on L1, an empty L2, a welder on L3: that identity is gone. Total P is P1 + P2 + P3. S is not √3 · U · Iaverage. Size the cable for the hottest phase, not for a polite mean.

Q can even change sign from phase to phase. The calculator on this page will still run; it will still be describing a balanced machine that you no longer have.

Neutral current: zero when balanced, alarming with non-linear loads

Balanced linear wye: the three currents cancel, IN = 0, the neutral is a spare. Unbalanced linear: the residual is the vector sum, and a simple magnitude check (if you assume 120° displacements) is

IN = √(I1² + I2² + I3² − I1I2 − I2I3 − I3I1)

Triplen harmonics (3rd, 9th, …) do not cancel. They add in the neutral. A floor of IT kit can push IN above any phase current, which is the surprise that melts a undersized neutral. Full-size the neutral, or a Dy11 transformer plus some filtering, if that is the load.

From line current to cable size and breaker rating

Start from I = P / (√3 · U · cos φ), or from the motor nameplate current — the nameplate already includes the real cos φ and efficiency. Then diversity (not everything at once) and a utilisation on the circuit, in the IEC 60364 / BS 7671 sense of how hard that circuit is actually loaded.

  1. Find design current Ib.
  2. Pick a protective device In ≥ Ib (motors often want a 1.25 factor and a D or motor curve for the inrush).
  3. Pick a cable whose tabulated Iz ≥ In, after grouping and ambient derating.
  4. Check voltage drop — often 3 % on lighting, 5 % on power, of the nominal U — which on a long run sizes the copper, not the ampacity.

This page gives you I. The tables give you mm². They are not the same book.

The other spelling: P = 3 · V · I · cos φ

Same three-phase power, phase voltage, line current, three phases. Useful when you are staring at a 230 V winding current in star. The √3 form is useful when you have a clamp on a 400 V feeder and no interest in V. Pick one and stay with it for the rest of the sum.

Why a VFD does not want a naive capacitor

The rectifier already draws a peaky current. Park a capacitor on the same bus without a detuning reactor and you have a tank circuit looking for the 5th harmonic. Correction for a drive is an active front end, a DC choke, or a detuned / active filter — not a lump of kvar on the terminals. The Qc line on this page is for linear lagging loads: motors, welders, the old inductive plant.

50 Hz, 60 Hz, and a √3 that does not care

The geometry is 120°, not 50. A 480 V 60 Hz motor uses the same formulas with its own U, I and cos φ. Frequency changes the motor's synchronous speed and the capacitor's kvar (Q = U² · 2πfC), not the √3 on the power triangle.

Every formula on this page is a balanced, sinusoidal three-phase set. Unbalanced currents, a missing phase, or a VFD full of harmonics will still produce a number if you type three figures in. That number is not the current in the cable. Measure, or split the sum phase by phase.