Star-Delta Motor Starting Calculator
A direct-on-line start can draw 5 to 8 times the motor's rated current for a few seconds — enough to disturb the supply and put real stress on the windings. Star-delta starting reduces this inrush by first energising the motor in star connection (reduced voltage across each winding), then switching to delta once the motor has picked up enough speed.
This page is not about converting a resistor network between star and delta (Kennelly's theorem, an unrelated topic despite the similar name) — this one is genuinely about starting a motor.
Motor and load characteristics
Result
The torque available in star (65 N·m) exceeds the load's starting torque (29 N·m): star-delta starting is viable with this load.
- Line current in star 68 A
- Line current direct-on-line 203 A
- Torque in star 65 N·m
- Voltage per winding in star 231 V
| Voltage per winding (star) | 231 V |
| Line current — direct-on-line | 203 A |
| Line current — star connection | 68 A |
| Starting torque — direct-on-line | 194 N·m |
| Starting torque — star connection | 65 N·m |
| Load starting torque | 29 N·m |
The calculation, in detail
Iline, star = Iline, direct ÷ 3
Cstarting, star = Cstarting, direct ÷ 3
Uwinding, star = Usupply ÷ √3
The factor of 3 comes from combining two effects: the voltage across each winding is reduced by √3 in star compared with delta, and the line current in star equals the winding current (whereas in delta it equals √3 times the winding current) — the product of both effects (1/√3 on the voltage, hence the winding current, times a further 1/√3 between winding current and line current) gives 1/3 on the line current. Torque, proportional to the square of the applied voltage at a given slip, undergoes the same reduction by a factor of (√3)² = 3.
Setting the star-to-delta transition timer: too early or too late both cause problems
The motor has to reach a good fraction of rated speed in star — typically 75–90 % — before you close delta. The timer is not a decoration. Too short, and you dump the motor into delta while it is still drawing a large slip current: the inrush you thought you had divided by three comes back as a second kick, and the load may not have enough torque to keep accelerating. Too long, and the motor sits in star with reduced voltage on the windings, cooking itself at high slip, never making enough torque to finish the start.
A current relay (transition on current, not on a stopwatch) is kinder: it waits until the star current has fallen, which is a decent proxy for “speed is up”. A timer is what most cheap starters ship with. Set it on the real load, not on the empty shaft in the workshop. A pump against a closed discharge valve is not the same start as a fan that has to push air from the first turn.
The current spike at the star-to-delta transition, often overlooked in simple calculations
This page divides DOL current and torque by three. That is the star connection, while the motor is in star. The ugly bit is the changeover. Open-transition starters open the star contactor, wait a beat (50–100 ms), then close delta. For that beat the motor is a spinning magnet with nowhere to put its energy. Residual flux and the supply are not in phase when delta closes. The result can be a transient line current as high as — or higher than — a DOL start, lasting a cycle or two.
Closed-transition starters (a resistor or autotransformer step between star and delta) tame that spike. They cost more, so a lot of plant still uses open transition and lives with a blink on the lights. If the reason you fitted star-delta was a weak supply that cannot stand DOL, check that the transition spike is not the thing that actually trips the breaker. The factor-of-three on this page will not warn you.
Wiring diagram and the role of the three contactors (line, star, delta)
A standard star-delta starter is three contactors and an interlock, not one big switch.
- Line (or main) contactor KM1 — closes first, stays closed. Feeds L1, L2, L3 to U1, V1, W1.
- Star contactor KM2 — closes with KM1 at start, shorts U2, V2, W2 together. That is the star point. It must drop out before delta closes.
- Delta contactor KM3 — closes after the timer, connecting U1–W2, V1–U2, W1–V2 (or the permutation on the drawing). Mechanical and electrical interlock with KM2: star and delta must never be in together, or you have a phase-to-phase short.
The motor needs six leads brought out (U1 V1 W1 U2 V2 W2). A three-lead motor with an internal star or delta cannot do this start. Check the terminal box before you order the starter. Contactor KM3 is sized for the delta line current; KM2 only carries the star winding current during a few seconds, so it can be a frame smaller — follow the manufacturer's table rather than inventing a derating.
Alternatives: soft starters and variable frequency drives, when to prefer them
Star-delta is cheap, well understood, and crude. Two other answers to the same inrush:
- Soft starter — thyristors ramp the voltage. Current is a setting, not a factor of three. Torque ramps with V², so you can start a load that star-delta would stall, provided you accept a longer run-up and more heating. No six-lead requirement. At full speed the bypass contactor takes over and the thyristors sit idle.
- VFD — frequency and voltage ramp together (constant V/f). Starting current around 1.5–2 × In, starting torque up to rated if you want it. Speed control afterwards, which star-delta will never give you. Cost, harmonics, a cubicle — see the running-cost page if the drive also has an energy case.
Pick star-delta when the load is easy to accelerate (fan, unloaded compressor, pump with a foot valve), the motor is six-lead, and nobody needs speed control. Pick a soft starter when the supply is weak and the torque still has to be more than a third of DOL. Pick a VFD when you needed variable speed anyway, or the mechanical shock of a star-delta changeover is the actual problem.
Limits of star-delta starting on high-starting-torque loads
Torque in star is one third of DOL torque. If the load needs 60 % of rated torque to break away — a loaded conveyor, a crusher, a mixer sitting in cold product — star-delta simply will not start. The shaft twitches, current stays high, the timer expires, and delta closes on a motor that is still near standstill. That is a DOL start with extra steps, plus a toasted starter if you repeat it.
This calculator's torque check is the one that matters. If Cstar is below the load breakaway torque, stop. Do not “give it a longer timer”. The physics will not arrive. Unload the machine, fit a soft starter or a VFD, or pick a motor with a higher starting-torque code.
Starting current code letters (IEC/NEMA) and how they relate to Id/In
Nameplates do not all say “Id/In = 7”. IEC motors often give a locked-rotor current in amps, or a designation. NEMA uses a locked-rotor kVA code letter (A to V): code G is 5.6–6.3 kVA/hp, code K is 8.0–9.0, and so on. Convert kVA/hp to a current multiple with the rated voltage and the horsepower, and you have Id/In for this form.
Id / In ≈ (kVA/hp × 1,000) / (U × In / hp)
A typical IEC 4-pole cage motor sits around 6–8 × In DOL. High-efficiency designs can be worse (more like 8–10), because lower resistance is good for running losses and bad for locked-rotor current. Do not assume 7 because a textbook said 7. Read the plate, then divide by three for star.
Six terminals, one voltage, and the nameplate 230/400 V trap
Star-delta starting only works when the delta voltage of the motor matches the supply. A 230/400 V motor on a 400 V line is a star motor in service; you cannot start it in star and run it in delta, because delta would put 400 V on 230 V windings. You need a 400/690 V motor (delta at 400 V, star at 690 V) to star-delta start on 400 V.
That is the most common ordering mistake. The starter is fine. The motor is wound for the wrong pair. Check both numbers before you pull six cores to the terminal box.
How long the start may last
Star is a reduced-voltage, high-slip regime. The rotor losses are large. IEC duty S1 motors tolerate only a handful of seconds — sometimes up to 10–15 s on a light fan, much less on a high-inertia load. Repeated starts without cooling time stack that heat. The datasheet's “starts per hour” is not a suggestion.
What the factor of three does not cover
The ÷3 on current and torque is a steady-state star connection versus a steady-state delta connection, at the same slip. It is not the rms of the transition, not the thermal equivalent current, and not a permit to downsize the upstream fuse to a third. The short-circuit rating of the starter still has to clear a fault in delta.
Never close star and delta together. The interlock is there because a welded contact on KM2 plus a close on KM3 is a bolted short on the supply. If a contactor has welded, stop and replace it — do not “just try again”.