Transformer Turns Ratio Calculator
The turns ratio m of a single-phase transformer links its voltages (m = U2/U1) to its number of turns (m = N2/N1): it's the same number, whether you're talking voltage or winding. For an ideal transformer (no losses), the apparent power is the same on both sides, which gives the rated primary and secondary currents directly.
Enter what you know — both voltages, or both turn counts — along with the transformer's rated apparent power S.
The transformer
How a transformer works: mutual induction between two coils
Two windings share a magnetic circuit. AC in the primary sets up an alternating flux in the core; that flux links the secondary and Faraday does the rest: e = −N dΦ/dt. Same flux, two turn counts, two voltages. No sliding contacts, no electrical connection required between the two sides (unless you add one on purpose). That is a transformer, not a rotary converter.
The ideal picture used on this page — m = U2/U1 = N2/N1, and S = U1·I1 = U2·I2 — assumes perfect coupling, no leakage, no winding resistance, no core loss. A 50 VA control transformer is close enough for sizing. A current transformer, a welding transformer, a 400 kVA distribution unit: same idea, more footnotes.
Step-up or step-down: reading the ratio m either way
This calculator defines m = U2/U1 = N2/N1. m > 1 is a step-up: more turns on the secondary, higher voltage, lower current. m < 1 is a step-down. Some textbooks write the ratio as a:b meaning primary:secondary turns, others as Up/Us. There is no international police for this. Write which side is which, or you will energise a 230 V winding from 24 V and wonder why nothing happens — or the other way round, which is worse.
m = U2 / U1 = N2 / N1 = I1 / I2 (ideal, no magnetising current)
The current ratio is the inverse of the voltage ratio because apparent power is conserved in the ideal machine. Step the voltage down by ten, the available current goes up by ten. That is why a 24 V, 10 A bell transformer is a 240 VA device, not a 24 W curiosity.
The real transformer: iron losses, copper losses, efficiency
Two loss buckets. Iron (core) losses — hysteresis plus eddy currents — depend on flux and frequency. They run whenever the primary is energised, load or no load. Copper losses — I²R in both windings — follow the square of the load current. Efficiency is Pout / (Pout + Piron + Pcopper), and it peaks where those two buckets are equal, usually around half to full load depending on the design.
A distribution transformer might sit at 97–99 % at full load. A tiny PCB transformer can be 80 % and still be correctly designed: the iron is a larger fraction of a small VA. The currents on this page are rated currents from S/U, not measured currents. They ignore magnetising current and they ignore the extra amps that cover the losses. Fine for a first size. Tight for a protection study.
Magnetizing current and no-load current: why they exist
The core needs an amp-turn to set up the flux. That is the magnetising current, in quadrature with the voltage (it looks like an inductor). A small in-phase slice covers the iron losses. Together they are the no-load current I0, typically a few percent of rated current on a decent power transformer, more on a cheap EI-core control transformer. I0 is why a transformer on the bench still hums and still draws a little current with the secondary open.
Inrush is a different spike: close the primary at a voltage zero and the flux can demand a remnant-plus-peak that saturates the core. Peak inrush of 8–12 × In for a few cycles is normal. A breaker that is “right” for the rated current may still nuisance-trip on energisation. That is not this calculator, but it is why a transformer feeder is not sized like a heater.
Isolation transformers, safety transformers (SELV)
Any two-winding transformer isolates, galvanically, if you do not bond a secondary terminal to the primary earth. An isolation transformer is built and tested for that job: reinforced or double insulation, a screen sometimes, a rating plate that says so. A safety extra-low voltage (SELV) transformer (IEC 61558) goes further: secondary not exceeding 50 V AC, isolated, and constructed so a single fault cannot put mains on the extra-low side.
Turns ratio alone does not make a SELV supply. A 230/12 V autotransformer shares a winding and is not isolated at all — one broken connection and the “12 V” terminal is hanging on the mains. If you needed isolation, you needed two windings and the right standard, not just m = 12/230.
Sizing a transformer's apparent power for an application
Transformers are rated in VA (or kVA), not in watts. The winding copper cares about current; the core cares about voltage and frequency. Power factor lives on the load. A 1,000 W heater at unity pf is 1 kVA. A 1,000 W of small motors at 0.7 pf is 1.4 kVA. Size S ≥ P / cos φ, then add a margin for inrush, harmonics (a rectifier load draws a peaky current that heats the winding harder than its rms suggests), and ambient.
S ≥ P / cos φ · I1 = S / U1 · I2 = S / U2
This page will compute I1 and I2 from the S you type. It will not tell you whether that S is enough. If the load is a VFD or a bank of LEDs, derate or pick a K-factor transformer. If it is a motor, remember the DOL inrush is on the secondary and reflects to the primary divided by m.
Three-phase transformers: star, delta, zigzag connections
A three-phase unit is three windings (or a single core with three legs) connected star (Y), delta (D) or zigzag (Z) on each side. The combination is a vector group: Dyn11, YNd5, Yzn11 and so on. The letter is the connection, the number is the clock face of the secondary phasor relative to the primary. Dyn11 is a delta primary, star secondary, 30° lag — the common distribution transformer that gives you a neutral.
- Star — a neutral, phase voltage = line/√3, good for mixed single-phase loads.
- Delta — no neutral, a circulating path for triplen harmonics, line current = √3 × winding current.
- Zigzag — a neutral with a better handle on unbalanced earth fault current; used as an earthing transformer or a special secondary.
The turns ratio of each limb is still N2/N1. The line-to-line voltage ratio also depends on whether a √3 appeared because one side is star and the other delta. Do not type a Dyn11 nameplate pair into this single-phase calculator and expect the currents to match the three-phase formula. Use the three-phase power page for the √3, and this page for one limb.
Short-circuit and short-circuit voltage Ucc: what it means
Ucc (or Z%) is the voltage you must apply to the primary, secondary shorted, to push rated current. 4 % to 6 % is typical for a distribution transformer; large units go higher. It is the per-unit impedance of the transformer. Fault current on the secondary is roughly In / (Ucc/100). A 6 % Ucc means about 16 × In if the supply is stiff. That number sizes the secondary protection and the busbars, not the turns ratio.
A low Ucc is a “stiff” transformer: small voltage drop on load, large prospective fault current. A high Ucc drops more voltage when the load comes on, which is why a welder transformer is built leaky on purpose. This calculator's ideal S = U·I ignores that drop. At full load a 5 % Ucc has already given away 5 % of the secondary voltage if the impedance is mostly reactive.
Polarity, dots, and connecting windings in parallel
The dot convention says which ends of the two windings go positive together. Get it wrong and two paralleled secondaries fight: a circulating current limited only by Ucc. Additive series (a 230 + 230 auto-like stack of two isolated windings) needs the same care. The turns ratio does not encode polarity. The nameplate vector group, or a simple flick test with a low-voltage source and a voltmeter, does.
Frequency, volts per turn, and a 60 Hz nameplate on 50 Hz
Flux is U / (4.44 f N A). Drop the frequency, keep the voltage, and the core walks toward saturation. A 60 Hz transformer on 50 Hz wants about 5/6 of its rated voltage, or a core that was oversized to begin with. The turns ratio is unchanged. The VA rating may not be. The other way (50 Hz kit on 60 Hz) is kinder on flux and slightly unkind on cooling and eddy currents.
What this page treats as ideal
No magnetising current in I1, no regulation, no Ucc, efficiency 100 %. The numbers are the rated currents of an ideal single-phase transformer at the S you typed. They are the right starting point for a turns count and a fuse size on a small unit. They are not a short-circuit study.
An autotransformer uses a single winding as both primary and secondary. The turns ratio still sets the voltages; the current in the shared section is the difference of the two line currents, and there is no galvanic isolation. Do not size an autotransformer as if S = U2·I2 were the winding throughput — the winding is smaller than that, and a fault on the secondary can put mains on the load.