Induction motor calculator: slip, speed and torque
An induction motor always turns slower than the rotating field of its stator. That shortfall — the slip — is not a fault: it is what induces current in the rotor, and therefore what makes torque. A motor that reached synchronous speed would deliver nothing at all.
From the figures on a nameplate alone, this calculator gives you synchronous speed, slip, shaft torque, the power actually drawn from the supply and the line current.
The power stamped on the plate is the output power, available at the shaft. The input power is higher by the efficiency, and it is the input that sets the current — hence the protection and the cable size.
The nameplate
The rotating field: how three windings 120° apart make a rotor turn
Three stator windings, 120° apart in space, fed with three currents 120° apart in time. The magnetic field they make does not sit still: it travels around the air gap at synchronous speed. That rotating field cuts the rotor bars. Currents appear in the cage (the bars are shorted by the end rings). Those currents make their own field, which tries to catch the stator field. The rotor turns. No brushes, no slip rings on a squirrel-cage machine — the rotor is a casting.
That is induction: the rotor is a shorted transformer secondary that is allowed to spin. If you ever need a mental picture, it is a transformer whose secondary has been bent into a cylinder and put on bearings.
Why an induction motor can never reach synchronous speed
At exact synchronous speed, the rotor sees a stationary field. No cutting of flux, no induced current, no torque. Gravity and friction would win in a millisecond, the rotor would slip, current would return, torque would return. So the machine always runs a little slow. That difference is slip. Load it harder, slip grows, torque grows (until the peak). That is why it is an asynchronous motor, and why a nameplate 1,450 rpm on a 1,500 rpm field is not a defect.
s = (ns − n) / ns · ns = 120 · f / poles
A PM synchronous motor has magnets instead of a cage and locks to the field. Zero slip in steady state. Different page, different machine.
Poles or pole pairs: the confusion that doubles the speed you expect
The formula on this page uses the number of poles: 2, 4, 6, 8. A 2-pole motor is one pole pair and 3,000 rpm at 50 Hz (3,600 at 60 Hz). A 4-pole is two pairs and 1,500 / 1,800. Put pole pairs into a formula that wanted poles and you double the speed. The drop-down is there so nobody types “2” meaning “two pairs” on a 1,500 rpm motor.
- 2 poles — 3,000 rpm at 50 Hz (3,600 at 60)
- 4 poles — 1,500 (1,800)
- 6 poles — 1,000 (1,200)
- 8 poles — 750 (900)
The shaft is slower than that by the slip. 1,450 on a 50 Hz 4-pole plate is normal. 1,500 on that same plate would be a synchronous machine, or a typing error.
Reading a nameplate line by line, both connections included
Everything this calculator asks for is on the plate, if you read it coldly:
- Voltage — 230/400 V or 400/690 V. Lower is delta, higher is star. Wrong connection, wrong flux.
- Current — two numbers, one per connection (10.5/6.1 A is the usual shape).
- kW — shaft output, not input. Input is kW / η.
- rpm — full-load speed, already slipped.
- cos φ and η (or an IE class) at that load.
- Hz — 50 or 60, or both.
This page turns those figures into slip, torque, input power and line current. It does not check that you picked the current that matches the connection you actually landed on the terminals.
Output power, input power, iron losses, copper losses, friction losses
Nameplate kW is Pout, the shaft. The grid sees Pin = Pout / η. The difference is heat:
- Stator copper — I²R in the winding you can see.
- Iron — hysteresis and eddy currents in the stack, roughly constant with load if V/f is held.
- Rotor copper — slip × air-gap power. Small at full speed, large at start.
- Friction and windage — bearings and the fan on the shaft.
η = Pout / Pin · Pin = √3 · U · I · cos φ
A 15 kW motor at 92 % is dumping about 1.3 kW as heat at full load. That is why the frame has fins, and why a boxed-in motor on a 40 °C mezzanine is not the motor on the datasheet.
Full-load, starting and breakdown torque: the whole curve
Three numbers on a torque-speed curve, only one of which is the nameplate:
- Starting (locked-rotor) torque — at n = 0. Has to beat breakaway. Often 1.5–2.5 × full-load on a cage motor DOL.
- Breakdown (pull-out) torque — the peak, typically ~2 × full-load. Past that peak the curve falls and the motor stalls.
- Full-load torque — the continuous shaft torque at rated kW and rated rpm. What this calculator prints from T = P / Ω.
T (N·m) = 9,550 × PkW / nrpm
Useful torque on a light load is less than full-load torque. Starting torque is not a power: speed is zero. Do not feed it into the kW formula and expect a rating.
Slip and torque: the stable region, and the point where the motor pulls out
From no-load up to breakdown, more slip means more torque. The motor is stable: a sudden extra load slows it a fraction, torque rises, it holds. Beyond breakdown, more slip means less torque. The shaft falls into a stall, current soars, protection should trip. Rated operation lives well to the right of that peak, with Tmax / TFL often 2–2.5 as a cushion.
A supply dip, a jam, a VFD that ran out of current: those are how you meet the peak on purpose. A process that “usually” sits at 80 % of rated torque is still fine. One that sits at 180 % for a minute is a different motor, or a different gearbox.
Direct-on-line starting current: six to eight times full load, and how to cut it
Close a contactor on a stopped cage motor and the slip is 1. Rotor frequency is line frequency, rotor current is huge, stator current follows: 6–8 × In is ordinary, 8–10 on some high-efficiency designs (the copper you removed to gain IE3 comes back as inrush). A few seconds, a voltage dip on a weak supply, a thump in the coupling.
You cut it with star-delta, a soft starter, or a VFD — next section. You do not cut it by typing a smaller current into this calculator. Full-load I is a running number.
Star-delta, soft starter, variable-speed drive: three answers to one problem
- Star-delta — six leads, current and torque ÷3 in star, then a bump into delta. Cheap. The starting calculator sizes that bump.
- Soft starter — ramped voltage, current you can set, torque following V². No six-lead requirement. No speed control once it is up.
- VFD — ramped frequency and voltage, 1.5–2 × In at start, and then any speed you want. Harmonics, a cubicle, a reason to look at the running-cost page if the load is a pump or a fan.
Pick on torque, on the supply, and on whether you needed variable speed anyway. Inrush is only one of the three questions.
Changing speed by changing frequency: the constant V/f rule
ns tracks f. Drop frequency and keep voltage, flux rises, the core saturates, current and heat follow. Hold V/f constant and flux stays put: rated torque is still available down the speed range, until the shaft fan can no longer cool the frame. That is scalar control, the basic VFD for an induction motor.
V / f = constant (rated voltage / rated frequency)
Above base speed you run out of voltage (the inverter cannot make more than the supply). Field-weakening: torque falls as 1/n, power flattish. Below a few hertz, V/f needs a voltage boost to cover stator resistance, or you get a motor that will not break away. Vector control is the next step; this paragraph is the one that keeps a 4-pole motor from melting at 25 Hz, 400 V.
Efficiency classes IE1 to IE4: what one point of efficiency is worth on the bill
IEC 60034-30-1 bands full-load efficiency by power and poles, not by a single percentage. IE1 is the old standard cage. IE2 high. IE3 premium — the default new industrial motor in a lot of the world. IE4 super premium, still possible in a cage, more often a SynRM or a PM machine. IE5 is essentially not a squirrel cage.
One point, 50 kW, 4,000 h, 92 to 93 %: about 2,000 kWh/year. At €0.15 that is a few hundred euros, every year, for a premium you pay once. The replacement calculator is that sum with a purchase price on it. Low hours, already IE3: do not rip it out for a badge.
Induction motor or permanent-magnet synchronous: where the boundary falls
Cage motors: cheap, brutal, DOL, huge ratings, dirty rooms. Efficiency sags at light load. PM synchronous: compact, IE5 territory, no slip, wants a VFD, magnets that cost and that can demagnetise. The cost comparison is the hours-versus-purchase argument. Harsh plant and megawatts stay induction. Variable-speed, high hours, a tight envelope: the PM machine has been eating that lunch for a decade.
Squirrel cage versus a slip-ring rotor
The cage is the default. A wound-rotor (slip-ring) machine brings the rotor winding out so you can park starting resistors in it: high starting torque, lower inrush, old cranes and mills. Brushes to maintain, rings to wear, a technology a VFD has mostly retired. If the plate says “rotor V / A”, you do not have a cage, and star-delta is not the starter you were thinking of.
Duty S1, service factor, and a motor that is not 15 kW in a box
S1 is continuous. S3 is intermittent, S6 continuous with a periodic duty, and so on. A 15 kW S1 motor is 15 kW all day at 40 °C. The same frame in S3–40 % can carry more for a few minutes and then must rest. NEMA service factor (1.15) is a cousin of that idea. This calculator uses the kW you type as if it were S1 continuous. A mill motor on a 15-minute cycle is a different thermal story.
Insulation, dV/dt, and a VFD-rated winding
A drive puts steep voltage pulses on the terminals. Long cables ring; the first turns of the winding see more than the DC bus. A motor that was happy DOL can flash over on a 50 m unfiltered lead. Inverter-duty insulation (or a dV/dt filter) is not snobbery. Neither is a separately blown cooling fan if you plan to crawl at rated torque.
Poles, not pole pairs. Output kW, not input. Full-load current, not starting current. The plate is the input; the formulas on this page only rearrange it. A 230/400 motor star-connected on 400 V is the usual right answer — delta on that supply is the usual way to let the smoke out.